Chi tiết sản phẩm
Tủ thiết bị cắt sét HSRF-63 1F




Đặc tính
HSRF-63 1F is a combination of two stage surge reduction protection device & high frequency filter with first rate effectivity. HSRF
comply with requirements of EN 61643-11 & IEC 61643-1 standards. HSRF is recommended for use in the Lightning Protection Zones
Concept at the boundaries of LPZ 0 – 2 (acc. to IEC 1312-1 and EN 62305) for lightning current equipotential bonding in power supply
systems applications.
Thông số kỹ thuật
HSRF-63 1F is a combination of two stage surge reduction protection device & high frequency filter with first rate effectivity. HSRF
comply with requirements of EN 61643-11 & IEC 61643-1 standards. HSRF is recommended for use in the Lightning Protection Zones
Concept at the boundaries of LPZ 0 – 2 (acc. to IEC 1312-1 and EN 62305) for lightning current equipotential bonding in power supply
systems applications.
HSRF is to be placed as near to the protected appliances as possible, for example near to electronic control systems of NC machines,
electronics of robotic production and another sensitive electronic appliances.
HSRF is offered in standard waterproof metal box with inbuilt optical diagnostic control panel of right function. In addition it is equipped
with internal accoustic alert and potential free changeover remote damage contact.
Type Hakel Surge Reduction Filter HSRF-63 1F
Classification acc. to EN 61643-11 Type 1+2+3
Classification acc. to IEC 61643-1 Class I+II+III
Nominal voltage UN 230/400VAC
Max. continual operating voltage UC 275/480VAC
System compatibility TNC, TNS, TT
Frequency f 50/60Hz
Max. line current IL 40Arms // 1 phase
Protection mode L-N, N-E, L-E
Protection circuit Spark gap / MOV / low pass filter
Max. surge current Imax 130kA(8/20) // 1 phase
Max. lightning current (L-N) Iimp 60kA(10/350) // 1 phase
Charge Q 30Asec // 1 phase
Specific energy W/R 900kJ/Ω // 1 phase
<780V at 5kA(8/20)
Voltage protection level (L-N) U <780V at 20kA(8/20)
<780V at 50kA(8/20)
Max. lightning current (N-E) Iimp 100kA(10/350)
Charge Q 50Asec
Specific energy W/R 2500kJ/Ω
<840V at 5kA(8/20)
Voltage protection level (N-E) U <840V at 20kA(8/20)
<840V at 50kA(8/20)
Filtering min. 60dB / 100kHz
Power dissipation at IL PN 15 W
Recommended external
1 x 63 A gL/gG
overcurrent protection
Alert by 1 LED light for 1. stage on front panel of box
Status control Alert by 1 LED light for 2. stage on front panel of box
Remote changeover contact for damage 1.& 2.stage
Ambient temperature working range -40 to 50°C
Recommended cross section
2
35 mm Cu
of connection wires
Dimensions HxDxW 400x155x300
Weight m 9,5 kg
Box / housing Steel waterproof box / IP 55
Article number 10 275
the queen of power